Subject: RECV bug in transport TCP layer
Date: Mon, 12 Nov 2012 09:36:13 +0000
To: "bug-Protocol-Modbus [...] rt.cpan.org" <bug-Protocol-Modbus [...] rt.cpan.org>
From: Martin Nørby Nielsen <mnni [...] dtu.dk>
Download (untitled) / with headers
text/plain 853b
Hey I found a data receive limit when I was trying to read more than 46 registers at once the limit should be 123 words. I debugged the problem to the receive line in \transport\TCP.pm line 71 $sock->recv(my $data, 100); please correct to: $sock->recv(my $data, 256); This should make it possible to receive 123 registers including the overhead : maximum according to the TCP modbus standard thanks for some sweet code I use it to interface with LAB PLC's kind regards Martin Nørby Nielsen Udviklingsingeniør Department of Energy Conversion and Storage Danmarks Tekniske Universitet [dtu] DTU Risø Campus, P.O. Box 49 Frederiksborgvej 399, P.O. Box 49 Bygning 227 4000 Roskilde Direkte telefon +45 4677 5634 mobile: + 45 2136 3137 mnni@risoe.dtu.dk<mailto:mnni@risoe.dtu.dk> www.risoe.dtu.dk<http://www.risoe.dtu.dk/>
Download image001.gif
image/gif 58b
image001.gif
Download image002.gif
image/gif 1k
image002.gif
Download (untitled) / with headers
text/plain 119b
Martin, thanks for your feedback. Sorry for the late answer, but 0.10 with the suggested change is on its way to CPAN.